Description / SCHNEIDER ELECTRIC TSXPSY5500M 072562Power supply module, Modicon Premium, input current of 1700mA, secondary power of 50W, 85 to 140VAC and 190 to 264VAC:, Specifications, Main, Range of Product, Modicon Premium Automation platform, Product or Component Type, Power supply module, Complementary, Primary voltage, 100...120 V AC 85...140 V, 200...240 V AC 190...264 V, Network Frequency, 50/60 Hz, network frequency limits, 47…63 Hz, Input current, 1700 mA 100 V, 500 mA 240 V, Inrush current, 38 A 100 V, 38 A 240 V, I²t on activation, 2 A².s 240 V, 4 A².s 100 V, It on activation, 0.11 A.s 100 V, 0.11 A.s 240 V, Protection type, Internal fuse 4 A 5 x 20 mm time-delayed primary circuit, Overload protection secondary circuit, Overvoltage protection secondary circuit, Short-circuit protection secondary circuit, Total useful secondary power, 50 W, Secondary power, 19 W 24 V DC, 35 W 5 V DC, Current at secondary voltage, 0.8 A 24 V DC relay power supply, 0.8 A 24 V DC sensor power supply, 7 A 5 V DC, Insulation resistance, >= 100 MOhm primary/ground, >= 100 MOhm primary/secondary, Marking, CE, Local signalling, For presence of sensor voltage (24V) 1 LED (green), for presence of voltages (OK) 1 LED (green), for battery fault (BAT) 1 LED (red), module format, Double, Net Weight, 1.37 lb(US) (0.62 kg), Environment, Immunity to microbreaks, 10 ms, Dielectric strength, 2000 V primary/earth, 2000 V primary/secondary, Standards, 73/23/EEC, CSA C22.2 No 142, CSA C22.2 No 213 Class I Division 2 Group C, 92/31/EEC, UL 508, CSA C22.2 No 213 Class I Division 2 Group D, CSA C22.2 No 213 Class I Division 2 Group B, CSA C22.2 No 213 Class I Division 2 Group A, IEC 61131-2, 89/336/EEC, 93/68/EEC,Product Certifications, RMRS, LR, ABS, GL, RINA, DNV, BV, Ambient Air Temperature for Operation, 32…140 °F (0…60 °C), Ambient Air Temperature for Storage, -13…158 °F (-25…70 °C), Relative Humidity, 10…95 % without condensation for operation, 5…95 % without condensation for storage, Operating altitude, 0...6561.68 ft (0...2000 m), Protective treatment, TC, IP Degree of Protection, IP20, Pollution degree, 2